Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 18, 2014, 07:15 AM
  • 15 0008_15 0007_20141117_232154.mp4

Date
11/17/2014
W/O
470269
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00622
PipeID
P11896
Time
11:15 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1862
Sewer Name
15 PUENTE TRUNK
City
LA PUENTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
WO_0470269_TV15026_2014OCTOBER_1
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
15 0008
Downstream MH
15 0007
Dir. of Survey
Downstream
Length Surveyed
111.9 ft.
Total Length
111.9 ft.
Structural Index
1
Structural Quick
1100
Structural Rating
1
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
1
Overall Quick
Overall Rating
1
Pipe schematic from manhole 15 0008 to 15 0007
MH: 15 0008MH: 15 0007downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 00080 ft. MWM - Water Mark, 15 %of cross sectional area7.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"35.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"57.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"64.4 ft. CC - Crack Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES80.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"109 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"111.9 ft. MGO - General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE111.9 ft. AMH - Downstream Manhole, Survey Ends - 15 0007

Observation photos (11)

  • Water Level, 10 %of cross sectional area

    0 ft. - Water Level, 10 %of cross sectional area

  • Upstream Manhole, Survey Begins - 15 0008

    0 ft. - Upstream Manhole, Survey Begins - 15 0008

  • Water Mark, 15 %of cross sectional area

    0 ft. - Water Mark, 15 %of cross sectional area

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    7.3 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    35.2 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    57.5 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES

    64.4 ft. - Crack Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    80.3 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    109 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE

    111.9 ft. - General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE

  • Downstream Manhole, Survey Ends - 15 0007

    111.9 ft. - Downstream Manhole, Survey Ends - 15 0007

Observations (11)

DistanceCodeObservation
111.9MGOCONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE
0MWL
64.4CC
57.5TFC
0AMH15 0008
7.3TFC
109TFC
0MWM
80.3TFC
35.2TFC
111.9AMH15 0007

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-11-17T23:15:20-08:00
documentation
PROPIPE
is_lateral_inspection
false