Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 17, 2014, 11:16 AM
  • 15 0013A_15 0013_20141117_032841.mp4

Date
11/17/2014
W/O
470269
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00622
PipeID
P11902
Time
3:16 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1861
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
WO_0470269_TV15026_2014OCTOBER_1
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
15 0013A
Downstream MH
15 0013
Dir. of Survey
Downstream
Length Surveyed
263.5 ft.
Total Length
263.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2E00
O&M Rating
60
Overall Index
2
Overall Quick
Overall Rating
60
Pipe schematic from manhole 15 0013A to 15 0013
MH: 15 0013AMH: 15 0013downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 0013A0 ft. MGO - General Observation - CONNECTION AT MANHOLE 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area46.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"49.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"101.5 ft. DSGV - Deposits Settled Gravel, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start103.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"108.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"150.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN167.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"209.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"218.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"244.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"252.9 ft. DSGV - Deposits Settled Gravel, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish263.5 ft. AMH - Downstream Manhole, Survey Ends - 15 0013263.5 ft. MGO - General Observation - CONNECTION AT MANHOLE 9 O'CLOCK

Observation photos (17)

  • Upstream Manhole, Survey Begins - 15 0013A

    0 ft. - Upstream Manhole, Survey Begins - 15 0013A

  • General Observation - CONNECTION AT MANHOLE 9 O'CLOCK

    0 ft. - General Observation - CONNECTION AT MANHOLE 9 O'CLOCK

  • Water Level, 10 %of cross sectional area

    0 ft. - Water Level, 10 %of cross sectional area

  • Water Mark, 20 %of cross sectional area

    0 ft. - Water Mark, 20 %of cross sectional area

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    46.5 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    49.8 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Deposits Settled Gravel,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    101.5 ft. - Deposits Settled Gravel, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    103.5 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    108.8 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    150.2 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    167.3 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    209.3 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    218.1 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    244.5 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Deposits Settled Gravel,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Finish

    252.9 ft. - Deposits Settled Gravel, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish

  • Downstream Manhole, Survey Ends - 15 0013

    263.5 ft. - Downstream Manhole, Survey Ends - 15 0013

  • General Observation - CONNECTION AT MANHOLE 9 O'CLOCK

    263.5 ft. - General Observation - CONNECTION AT MANHOLE 9 O'CLOCK

Observations (17)

DistanceCodeObservation
0AMH15 0013A
209.3TFC
46.5TFA
263.5AMH15 0013
218.1TFC
0MGOCONNECTION AT MANHOLE 9 O'CLOCK
0MWL
108.8TB
244.5TFA
101.5DSGV
103.5TFC
150.2TFOPEN
0MWM
167.3TFC
252.9DSGV
49.8TFC
263.5MGOCONNECTION AT MANHOLE 9 O'CLOCK

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-11-17T03:16:49-08:00
documentation
PROPIPE
is_lateral_inspection
false