Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 10, 2014, 12:17 PM
  • 15 0040_15 0039_20141110_042359.mp4

Date
11/10/2014
W/O
470269
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00622
PipeID
P11930
Time
4:17 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1853
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
WO_0470269_TV15026_2014OCTOBER_1
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
15 0040
Downstream MH
15 0039
Dir. of Survey
Downstream
Length Surveyed
59.2 ft.
Total Length
59.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2A00
O&M Rating
24
Overall Index
2
Overall Quick
Overall Rating
24
Pipe schematic from manhole 15 0040 to 15 0039
MH: 15 0040MH: 15 0039downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 00400 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start9.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN35.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"59.2 ft. AMH - Downstream Manhole, Survey Ends - 15 003959.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (9)

  • Water Mark, 25 %of cross sectional area

    0 ft. - Water Mark, 25 %of cross sectional area

  • Upstream Manhole, Survey Begins - 15 0040

    0 ft. - Upstream Manhole, Survey Begins - 15 0040

  • Water Level, 15 %of cross sectional area

    0 ft. - Water Level, 15 %of cross sectional area

  • General Observation - CONNECTION AT MANHOLE 3 O'CLOCK

    0 ft. - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    9.1 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    35.9 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Downstream Manhole, Survey Ends - 15 0039

    59.2 ft. - Downstream Manhole, Survey Ends - 15 0039

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    59.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observations (9)

DistanceCodeObservation
59.2AMH15 0039
0MWM
0AMH15 0040
59.2DAGS
9.1TFOPEN
0MWL
0MGOCONNECTION AT MANHOLE 3 O'CLOCK
35.9TFC
0DAGS

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-11-10T04:17:03-08:00
documentation
PRO-PIPE
is_lateral_inspection
false