Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 10, 2014, 10:56 AM
  • 15 0044_H 0867_20141110_030838.mp4

Date
11/10/2014
W/O
470269
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00622
PipeID
P21415
Time
2:56 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1853
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
WO_0470269_TV15026_2014OCTOBER_1
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
15 0044
Downstream MH
H 0867
Dir. of Survey
Downstream
Length Surveyed
187.2 ft.
Total Length
187.2 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
312F
O&M Rating
77
Overall Index
2
Overall Quick
Overall Rating
79
Pipe schematic from manhole 15 0044 to H 0867
MH: 15 0044MH: H 0867downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 00440 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start0 ft. MWL - Water Level, 10 %of cross sectional area9.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE36.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"67.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"80.1 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES85.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN112.4 ft. TFI - Tap Factory Made Intruding, at 02 o'clock, -, #v, within 8 inches of joint: NO, 6", 4" - OPEN134.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"153.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"184 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish187.2 ft. AMH - Downstream Manhole, Survey Ends - H 0867

Observation photos (14)

  • Water Mark, 20 %of cross sectional area

    0 ft. - Water Mark, 20 %of cross sectional area

  • Upstream Manhole, Survey Begins - 15 0044

    0 ft. - Upstream Manhole, Survey Begins - 15 0044

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Water Level, 10 %of cross sectional area

    0 ft. - Water Level, 10 %of cross sectional area

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE

    9.5 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    36.6 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    67.1 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    80.1 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    85.7 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

  • Tap Factory Made Intruding, at 02 o'clock, -, #v, within 8 inches of joint: NO, 6", 4" - OPEN

    112.4 ft. - Tap Factory Made Intruding, at 02 o'clock, -, #v, within 8 inches of joint: NO, 6", 4" - OPEN

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    134.9 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    153.2 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    184 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

  • Downstream Manhole, Survey Ends - H 0867

    187.2 ft. - Downstream Manhole, Survey Ends - H 0867

Observations (14)

DistanceCodeObservation
112.4TFIOPEN
9.5TFACTIVE
153.2TFC
85.7TFOPEN
67.1TFC
36.6TFC
0MWM
134.9TFC
80.1CL
0AMH15 0044
184DAGS
187.2AMHH 0867
0DAGS
0MWL

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-11-10T02:56:50-08:00
documentation
PRO-PIPE
is_lateral_inspection
false