Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2014, 11:34 AM
  • 15 0021_15 0020_20141114_034818.mp4

Date
11/14/2014
W/O
470269
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00622
PipeID
P11910
Time
3:34 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1855
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_0470269_TV15026_2014OCTOBER_1
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
15 0021
Downstream MH
15 0020
Dir. of Survey
Downstream
Length Surveyed
272.2 ft.
Total Length
272.2 ft.
Structural Index
2
Structural Quick
2900
Structural Rating
18
O&M Index
2
O&M Quick
2J00
O&M Rating
112
Overall Index
2
Overall Quick
Overall Rating
130
Pipe schematic from manhole 15 0021 to 15 0020
MH: 15 0021MH: 15 0020downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start0 ft. MGO - General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 15 002158.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"64.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start110.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish114.2 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"169.5 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"210.1 ft. TBC - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"250.4 ft. TBC - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"270.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish272.2 ft. MGO - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE272.2 ft. MGO - General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE272.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0020

Observation photos (17)

  • Water Level, 10 %of cross sectional area

    0 ft. - Water Level, 10 %of cross sectional area

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE

    0 ft. - General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE

  • Water Mark, 20 %of cross sectional area

    0 ft. - Water Mark, 20 %of cross sectional area

  • General Observation - CONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE

    0 ft. - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE

  • Upstream Manhole, Survey Begins - 15 0021

    0 ft. - Upstream Manhole, Survey Begins - 15 0021

  • Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    58.2 ft. - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    64.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish

    110.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    114.2 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    169.5 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    210.1 ft. - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    250.4 ft. - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    270.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

  • General Observation - CONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE

    272.2 ft. - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE

  • General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE

    272.2 ft. - General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE

  • Downstream Manhole, Survey Ends - 15 0020

    272.2 ft. - Downstream Manhole, Survey Ends - 15 0020

Observations (17)

DistanceCodeObservation
0MWL
210.1TBC
0DAGS
114.2TBA
270.2DAGS
0MGOCONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE
0MWM
169.5TBA
272.2MGOCONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE
272.2MGOCONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE
272.2AMH15 0020
64.8CL
0MGOCONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE
250.4TBC
0AMH15 0021
58.2TFC
110.1CL

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-11-14T03:34:20-08:00
documentation
PROPIPE
is_lateral_inspection
false