Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 18, 2014, 08:18 AM
  • 15 0006 _H 0817_20141118_002833.mp4

Date
11/18/2014
W/O
470269
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00622
PipeID
P11894
Time
12:18 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1862
Sewer Name
15 PUNTE TRUNK
City
LA PUENTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
WO_0470269_TV15026_2014OCTOBER_1
Sewer Type
G
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
H 0817
Downstream MH
15 0006
Dir. of Survey
Upstream
Length Surveyed
80.7 ft.
Total Length
80.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole H 0817 to 15 0006
MH: H 0817MH: 15 0006upstream0 ft. AMH - Downstream Manhole, Survey Ends - ZOOMED IN TO MH H 8170 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES14.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"42.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"66.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"80.7 ft. MGO - Reversal Inspection80.7 ft. MWL - Water Level, 15 %of cross sectional area80.7 ft. MWM - Water Mark, 15 %of cross sectional area80.7 ft. AMH - Downstream Manhole, Survey Begins - H 0817

Observation photos (9)

  • Reversal Inspection

    0 ft. - Reversal Inspection

  • Water Level, 15 %of cross sectional area

    0 ft. - Water Level, 15 %of cross sectional area

  • Water Mark, 15 %of cross sectional area

    0 ft. - Water Mark, 15 %of cross sectional area

  • Downstream Manhole, Survey Begins - H 0817

    0 ft. - Downstream Manhole, Survey Begins - H 0817

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    14 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    37.8 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    66.6 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Downstream Manhole, Survey Ends - ZOOMED IN TO MH H 817

    80.7 ft. - Downstream Manhole, Survey Ends - ZOOMED IN TO MH H 817

  • Deposits Attached Grease, 20 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES

    80.7 ft. - Deposits Attached Grease, 20 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
0MGO
37.8TFC
66.6TFC
14TFC
80.7AMHZOOMED IN TO MH H 817
80.7DAGS
0MWL
0MWM
0AMHH 0817

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-11-18T00:18:20-08:00
documentation
PROPIPE
is_lateral_inspection
false