Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 17, 2014, 09:05 AM
  • 15 0018_15 0017_20141117_012653.mp4

Date
11/17/2014
W/O
470269
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00622
PipeID
P11907
Time
1:05 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1861
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_0470269_TV15026_2014OCTOBER_1
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
15 0018
Downstream MH
15 0017
Dir. of Survey
Downstream
Length Surveyed
347.5 ft.
Total Length
347.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
412M
O&M Rating
144
Overall Index
2
Overall Quick
Overall Rating
144
Pipe schematic from manhole 15 0018 to 15 0017
MH: 15 0018MH: 15 0017downstream0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 00180 ft. MGO - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE0 ft. MGO - General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE0 ft. MWL - Water Level, 10 %of cross sectional area15.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"68.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"117.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"118 ft. RMB - Roots Medium Barrell, at 12 o'clock, 10 %, within 8 inches of joint: NO - COMING OUT OF TAP165.4 ft. RFB - Roots Fine Barrell, at 12 o'clock, within 8 inches of joint: NO - COMING OUT OF TAP165.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"173.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"244.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"306.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"347.5 ft. MGO - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE347.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish347.5 ft. MGO - General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE347.5 ft. AMH - Downstream Manhole, Survey Ends - 15 0017

Observation photos (19)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Water Mark, 20 %of cross sectional area

    0 ft. - Water Mark, 20 %of cross sectional area

  • Upstream Manhole, Survey Begins - 15 0018

    0 ft. - Upstream Manhole, Survey Begins - 15 0018

  • General Observation - CONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE

    0 ft. - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE

  • General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE

    0 ft. - General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE

  • Water Level, 10 %of cross sectional area

    0 ft. - Water Level, 10 %of cross sectional area

  • Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    15.2 ft. - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    68.6 ft. - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    117.9 ft. - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Medium Barrell, at 12 o'clock, 10 %, within 8 inches of joint: NO - COMING OUT OF TAP

    118 ft. - Roots Medium Barrell, at 12 o'clock, 10 %, within 8 inches of joint: NO - COMING OUT OF TAP

  • Roots Fine Barrell, at 12 o'clock, within 8 inches of joint: NO - COMING OUT OF TAP

    165.4 ft. - Roots Fine Barrell, at 12 o'clock, within 8 inches of joint: NO - COMING OUT OF TAP

  • Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    165.4 ft. - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    173.3 ft. - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    244.3 ft. - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    306.7 ft. - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • General Observation - CONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE

    347.5 ft. - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    347.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

  • General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE

    347.5 ft. - General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE

  • Downstream Manhole, Survey Ends - 15 0017

    347.5 ft. - Downstream Manhole, Survey Ends - 15 0017

Observations (19)

DistanceCodeObservation
347.5MGOCONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE
0DAGS
118RMBCOMING OUT OF TAP
165.4RFBCOMING OUT OF TAP
117.9TFA
347.5DAGS
347.5MGOCONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE
0MWM
15.2TFC
244.3TFA
347.5AMH15 0017
306.7TFC
0AMH15 0018
165.4TFA
68.6TFA
0MGOCONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE
173.3TFC
0MGOCONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE
0MWL

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-11-17T01:05:09-08:00
documentation
PROPIPE
is_lateral_inspection
false