Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2014, 11:59 AM
  • 15 0019_15 0018_20141114_040510.mp4

Date
11/14/2014
W/O
470269
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00622
PipeID
P11908
Time
3:59 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1855
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_0470269_TV15026_2014OCTOBER_1
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
15 0019
Downstream MH
15 0018
Dir. of Survey
Downstream
Length Surveyed
94.1 ft.
Total Length
94.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2C00
O&M Rating
40
Overall Index
2
Overall Quick
Overall Rating
40
Pipe schematic from manhole 15 0019 to 15 0018
MH: 15 0019MH: 15 0018downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 00191.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start44 ft. TBC - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"94.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish94.1 ft. MGO - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE94.1 ft. AMH - Downstream Manhole, Survey Ends - 15 001894.1 ft. MGO - General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE

Observation photos (9)

  • Water Mark, 20 %of cross sectional area

    0 ft. - Water Mark, 20 %of cross sectional area

  • Water Level, 10 %of cross sectional area

    0 ft. - Water Level, 10 %of cross sectional area

  • Upstream Manhole, Survey Begins - 15 0019

    0 ft. - Upstream Manhole, Survey Begins - 15 0019

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    1.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    44 ft. - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    94.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

  • General Observation - CONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE

    94.1 ft. - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE

  • Downstream Manhole, Survey Ends - 15 0018

    94.1 ft. - Downstream Manhole, Survey Ends - 15 0018

  • General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE

    94.1 ft. - General Observation - CONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE

Observations (9)

DistanceCodeObservation
94.1DAGS
94.1MGOCONNECTION AT MANHOLE 3 O'CLOCK, ACTIVE
0MWM
94.1AMH15 0018
94.1MGOCONNECTION AT MANHOLE 9 O'CLOCK, ACTIVE
0MWL
0AMH15 0019
1.6DAGS
44TBC

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-11-14T03:59:23-08:00
documentation
PROPIPE
is_lateral_inspection
false