Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 12, 2014, 09:21 AM
  • 02 0826_02 0825_20141212_014428.mp4

Date
12/12/2014
W/O
464882
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00295
PipeID
P03392
Time
1:21 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K1749
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTION 3
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
TV02226
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0826
Downstream MH
02 0825
Dir. of Survey
Downstream
Length Surveyed
380 ft.
Total Length
380 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2N11
O&M Rating
151
Overall Index
2
Overall Quick
Overall Rating
151
Pipe schematic from manhole 02 0826 to 02 0825
MH: 02 0826MH: 02 0825downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 08260 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start73.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"175.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"276.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"376.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish377.8 ft. VC - Vermin Cockroach380 ft. AMH - Downstream Manhole, Survey Ends - 02 0825380 ft. MGO - General Observation - CONNECTION AT THE MH 9 O' CLOCK, UNKNOWN

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
276.8TFC
0AMH02 0826
380AMH02 0825
377.8VC
175.5TFA
0MWM
2DAGS
376.6DAGS
0MWL
380MGOCONNECTION AT THE MH 9 O' CLOCK, UNKNOWN
73.3TFC

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-12-12T01:21:52-08:00
documentation
PRO PIPE
is_lateral_inspection
false