Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 12, 2014, 11:03 AM
  • 02 0823_02 0822_20141212_032644.mp4

Date
12/12/2014
W/O
464882
Weather
Light Rain
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00295
PipeID
P03389
Time
3:03 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K1749
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTION 3
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
TV02226
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0823
Downstream MH
02 0822
Dir. of Survey
Downstream
Length Surveyed
298.7 ft.
Total Length
298.7 ft.
Structural Index
2
Structural Quick
3111
Structural Rating
4
O&M Index
2
O&M Quick
2K00
O&M Rating
118
Overall Index
2
Overall Quick
Overall Rating
122
Pipe schematic from manhole 02 0823 to 02 0822
MH: 02 0823MH: 02 0822downstream0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start0 ft. AMH - Upstream Manhole, Survey Begins - 02 08230 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area207.6 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES292.9 ft. CC - Crack Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES296.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish298.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0822

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    207.6 ft. - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES

    292.9 ft. - Crack Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
0DAGS
296.6DAGS
298.7AMH02 0822
292.9CC
0AMH02 0823
0MWM
0MWL
207.6CM

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-12-12T03:03:18-08:00
documentation
PRO PIPE
is_lateral_inspection
false