Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 12, 2014, 10:47 AM
  • 02 0825_02 0824_20141212_030227.mp4

Date
12/12/2014
W/O
464882
Weather
Light Rain
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00295
PipeID
P03391
Time
2:47 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K1749
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTION 3
City
PICO RIVERA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
TV02226
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0824
Downstream MH
02 0825
Dir. of Survey
Upstream
Length Surveyed
155.6 ft.
Total Length
155.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2E11
O&M Rating
63
Overall Index
2
Overall Quick
Overall Rating
63
Pipe schematic from manhole 02 0824 to 02 0825
MH: 02 0824MH: 02 0825upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 08250.1 ft. VC - Vermin Cockroach0.1 ft. MGO - General Observation - CONNECTION AT THE MH 3 O' CLOCK CAPPED2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish153.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start155.7 ft. MWM - Water Mark, 40 %of cross sectional area155.7 ft. AMH - Downstream Manhole, Survey Begins - 02 0824155.7 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
155.6VC
0MWM
0AMH02 0824
155.7AMH02 0825
2DAGS
153.4DAGS
155.6MGOCONNECTION AT THE MH 3 O' CLOCK CAPPED
0MWL

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-12-12T02:47:00-08:00
documentation
PRO PIPE
is_lateral_inspection
false