Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 12, 2014, 08:34 AM
  • 02 0829_02 0828_20141212_004416.mp4

Date
12/12/2014
W/O
464882
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00295
PipeID
P03395
Time
12:34 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K1749
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTION 3
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
22
Purpose
Routine Assessment
Project
TV02226
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0829
Downstream MH
02 0828
Dir. of Survey
Downstream
Length Surveyed
67.9 ft.
Total Length
67.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2B11
O&M Rating
27
Overall Index
2
Overall Quick
Overall Rating
27
Pipe schematic from manhole 02 0829 to 02 0828
MH: 02 0829MH: 02 0828downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 08290 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start65.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish67.9 ft. AMH - Downstream Manhole, Survey Ends - 02 082867.9 ft. MGO - General Observation - CONNECTION AT THE MH 9 O' CLOCK CAPPED67.9 ft. VC - Vermin Cockroach, within 8 inches of joint: YES

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
67.9AMH02 0828
0MWM
0AMH02 0829
67.9MGOCONNECTION AT THE MH 9 O' CLOCK CAPPED
2DAGS
67.9VC
65.3DAGS
0MWL

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-12-12T00:34:19-08:00
documentation
PRO PIPE
is_lateral_inspection
false