- Date
- 07/29/2021
- W/O
- 901971
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00005
- PipeID
- P00104
- Time
- 12:57 AM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K9203
- Sewer Name
- 08 EAST ROAD TRUNK
- City
- WEST CARSON
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 08
- Page No.
- 10
- Purpose
- Routine Assessment
- Project
- RFIR_WO_901971_TV08112_JUL2021
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 8 in.
- Width
- 12 in.
- Upstream MH
- 08 0230
- Downstream MH
- 08 0229
- Dir. of Survey
- Downstream
- Length Surveyed
- 352 ft.
- Total Length
- 352 ft.
- Structural Index
- 4
- Structural Quick
- 4M00
- Structural Rating
- 276
- O&M Index
- 2
- O&M Quick
- 412M
- O&M Rating
- 144
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 420
Pipe schematic from manhole 08 0230 to 08 0229 Observation photos (4)

0 ft. - General Observation - COCKROACHES IN MANHOLE

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

7.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

352 ft. - General Observation - COCKROACHES IN MANHOLE