Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 29, 2021, 09:14 AM
  • 08 0227_08 0226_07292021_022224.mp4

Date
07/29/2021
W/O
901971
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00005
PipeID
P00101
Time
2:14 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9203
Sewer Name
08 EAST ROAD TRUNK
City
WEST CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_901971_TV08112_JUL2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
12 in.
Upstream MH
08 0227
Downstream MH
08 0226
Dir. of Survey
Downstream
Length Surveyed
135.3 ft.
Total Length
135.3 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
75
O&M Index
2
O&M Quick
2D00
O&M Rating
52
Overall Index
2
Overall Quick
Overall Rating
127
Pipe schematic from manhole 08 0227 to 08 0226
MH: 08 0227MH: 08 0226downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 08 02270 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start44.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"53.8 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"112.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"132.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish132.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish135.3 ft. AMH - Downstream Manhole, Survey Ends - 08 0226135.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK135.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    135.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (15)

DistanceCodeObservation
0MWL
0MWM
0MGOCONNECTION AT MH 3 O'CLOCK
132.9CM
53.8TB
0AMH08 0227
44.3TFC
135.3AMH08 0226
2DAGS
132.9DAGS
0MGOCOCKROACHES IN MANHOLE
135.3MGOCONNECTION AT MH 3 O'CLOCK
7.3CM
112.6TFA
135.3MGOCOCKROACHES IN MANHOLE

Properties (5)

additional_info
630069072821203
customer
1
datetime
2021-07-29T02:14:13-07:00
documentation
PRO PIPE
is_lateral_inspection
false