Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 29, 2021, 09:52 AM
  • 08 0224_08 0223A_07292021_030510.mp4

Date
07/29/2021
W/O
901971
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00005
PipeID
P00098
Time
2:52 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9203
Sewer Name
08 EAST ROAD TRUNK
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_901971_TV08112_JUL2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0224
Downstream MH
08 0223A
Dir. of Survey
Downstream
Length Surveyed
280.2 ft.
Total Length
280.2 ft.
Structural Index
3
Structural Quick
513H
Structural Rating
134
O&M Index
2
O&M Quick
2T00
O&M Rating
206
Overall Index
2
Overall Quick
Overall Rating
340
Pipe schematic from manhole 08 0224 to 08 0223A
MH: 08 0224MH: 08 0223Adownstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 08 02242 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start36.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start47.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"61.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start98.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"150.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"197.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"248.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"277 ft. B - Broken, from 01 to 04 o'clock, within 8 inches of joint: YES277.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish277.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish277.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish280.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK280.2 ft. AMH - Downstream Manhole, Survey Ends - 08 0223A280.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    36.5 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    61.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 01 to 04 o'clock, within 8 inches of joint: YES

    277 ft. - Broken, from 01 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    280.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (20)

DistanceCodeObservation
36.5DAE
47.4TFC
61.3CM
0MGOCOCKROACHES IN MANHOLE
0MWL
0MWM
280.2MGOCONNECTION AT MH 9 O'CLOCK
277.5DAGS
280.2AMH08 0223A
277.5DAE
98.6TFC
248.3TFC
280.2MGOCOCKROACHES IN MANHOLE
277B
0MGOCONNECTION AT MH 3 O'CLOCK
197.1TFC
0AMH08 0224
150.2TFA
277.5CM
2DAGS

Properties (7)

additional_info
630069072821203
custom_field_three
BROKEN PIPE/CRACKS
custom_field_two
2
customer
1
datetime
2021-07-29T02:52:57-07:00
documentation
PRO PIPE
is_lateral_inspection
false