Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 30, 2021, 06:36 AM
  • 08 0216_08 0215_07292021_234344.mp4

Date
07/29/2021
W/O
901971
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00005
PipeID
P00086
Time
11:36 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9204
Sewer Name
08 EAST ROAD TRUNK
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_901971_TV08112_JUL2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
08 0216
Downstream MH
08 0215
Dir. of Survey
Downstream
Length Surveyed
44.3 ft.
Total Length
44.3 ft.
Structural Index
3
Structural Quick
4334
Structural Rating
24
O&M Index
2
O&M Quick
412B
O&M Rating
36
Overall Index
3
Overall Quick
Overall Rating
60
Pipe schematic from manhole 08 0216 to 08 0215
MH: 08 0216MH: 08 0215downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 02162 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start24.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start24.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish41.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish41.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish41.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish44.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE44.3 ft. AMH - Downstream Manhole, Survey Ends - 08 021544.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    24.7 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    44.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (15)

DistanceCodeObservation
41.5DAGS
41.5DAE
0MWM
44.3MGOCOCKROACHES IN MANHOLE
0MGOCOCKROACHES IN MANHOLE
0MWL
2DAE
44.3AMH08 0215
41.5FM
5CM
0AMH08 0216
44.3MGOCONNECTION AT MH 3 O'CLOCK
24.7FM
24.7CM
2DAGS

Properties (7)

additional_info
630069072921201
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2021-07-29T23:36:26-07:00
documentation
PRO PIPE
is_lateral_inspection
false