Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 27, 2021, 06:53 PM
  • 29 0524_29 0523_07272021_120424.mp4

Date
07/27/2021
W/O
901941
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01106
PipeID
P24576
Time
11:53 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9087
Sewer Name
29 19TH STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_901941_TV29072_JUL2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0524
Downstream MH
29 0523
Dir. of Survey
Downstream
Length Surveyed
238.2 ft.
Total Length
238.2 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
141
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
141
Pipe schematic from manhole 29 0524 to 29 0523
MH: 29 0524MH: 29 0523downstream0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 05240 ft. MWL - Water Level, 5 %of cross sectional area2.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"18.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"113.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"114.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"168 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"218.1 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"238.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish238.2 ft. AMH - Downstream Manhole, Survey Ends - 29 0523

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
168TF
113.8TF
238.2CM
0MWM
2.6CM
18.6TF
0AMH29 0524
218.1TF
0MWL
238.2AMH29 0523
114.7TF
6.2TF

Properties (7)

additional_info
630070072721053
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-07-27T11:53:33-07:00
documentation
PROPIPE
is_lateral_inspection
false