B 0737_B 0736_07272021_221407.mp4
2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start
9.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES
29.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start
105.7 ft. - Joint Offset Medium
107.8 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES
109.7 ft. - Broken Void Visible, from 06 to 08 o'clock, within 8 inches of joint: YES
126.6 ft. - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"
190.2 ft. - Fracture Spiral, from 06 to 09 o'clock, within 8 inches of joint: YES
251.8 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"
282.1 ft. - Fracture Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES
| Distance | Code | Observation |
|---|---|---|
| 282.1 | FS | — |
| 109.7 | BVV | — |
| 343.5 | MGO | CONNECTION AT MH, 3 O'CLOCK |
| 210.8 | TFA | — |
| 0 | MGO | CONNECTION AT MH, 9 O'CLOCK |
| 9.2 | CM | — |
| 126.6 | TBA | — |
| 29.6 | CM | — |
| 88.7 | DAGS | — |
| 0 | AMH | B 0737 |
| 343.5 | MGO | CONNECTION AT MH 9 OCLOCK CAPPED |
| 0 | MWM | — |
| 105.7 | JOM | — |
| 341.5 | CM | — |
| 110.9 | TF | — |
| 107.8 | DAGS | — |
| 0 | MWL | — |
| 312.1 | TFA | — |
| 2 | DAGS | — |
| 251.8 | TB | — |
| 190.2 | FS | — |
| 343.5 | AMH | B 0736 |