Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 27, 2021, 05:05 PM
  • 29 0372_29 0371_07272021_103103.mp4

Date
07/27/2021
W/O
901756
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01018
PipeID
P24409
Time
10:05 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9086
Sewer Name
29 21ST STREET TRUNK
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_901756_TV29076_JUL2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0372
Downstream MH
29 0371
Dir. of Survey
Downstream
Length Surveyed
456.8 ft.
Total Length
456.8 ft.
Structural Index
3
Structural Quick
4N3R
Structural Rating
575
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
575
Pipe schematic from manhole 29 0372 to 29 0371
MH: 29 0372MH: 29 0371downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 03720 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. MGO - General Observation - PIPE IS NRCP2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start13.1 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES52.7 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES85.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start117.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"129.2 ft. H - Hole, at 05 o'clock, within 8 inches of joint: NO181.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"247.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"277.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"349.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"378.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"452.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish456.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish456.8 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK456.8 ft. AMH - Downstream Manhole, Survey Ends - 29 0371

Observation photos (5)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    13.1 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    52.7 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    85.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Hole, at 05 o'clock, within 8 inches of joint: NO

    129.2 ft. - Hole, at 05 o'clock, within 8 inches of joint: NO

Observations (19)

DistanceCodeObservation
277.5TF
2.1MGOPIPE IS NRCP
13.1FM
247.1TF
0AMH29 0372
456.7SAV
349.7TF
0MWM
2.1SAV
85.6FM
117.7TF
181.8TF
52.7FL
0MWL
129.2H
378.5TF
452.1FM
456.8MGOCONNECTION AT THE MH 3 OC'LOCK
456.8AMH29 0371

Properties (7)

additional_info
630074072721052
custom_field_three
AGGREGATE VISIBLE/MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-07-27T10:05:09-07:00
documentation
PROPIPE
is_lateral_inspection
false