Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2021, 08:46 AM
  • H 0869_H 0489A_07262021_020340.mp4

Date
07/26/2021
W/O
901473
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00181
PipeID
P20460
Time
1:46 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9043
Sewer Name
H JOINT OUTFALL H - UNIT 6
City
BASSET
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
RFIR_WO_901473_TV15212_JUL2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
H 0869
Downstream MH
H 0489A
Dir. of Survey
Downstream
Length Surveyed
356.4 ft.
Total Length
356.4 ft.
Structural Index
3
Structural Quick
573M
Structural Rating
245
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
245
Pipe schematic from manhole H 0869 to H 0489A
MH: H 0869MH: H 0489Adownstream0 ft. MGO - General Observation - STOP LOG CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 08690 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start33.3 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish81.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"352.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES352.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish356.4 ft. AMH - Downstream Manhole, Survey Ends - H 0489A

Observation photos (3)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

    352.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0MGOSTOP LOG CONNECTION AT MH 3 O'CLOCK
33.3SRV
2SRV
0MWL
81.3TFA
0AMHH 0869
352.1SRV
2SAP
356.4AMHH 0489A
352.1SAP
0MWM

Properties (7)

additional_info
630069072621001
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-07-26T01:46:01-07:00
documentation
PRO PIPE
is_lateral_inspection
false