Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 29, 2021, 05:30 AM
  • 18 0929_18 0928_07282021_224848.mp4

Date
07/28/2021
W/O
901369
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00700
PipeID
P14777
Time
10:30 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9201
Sewer Name
18 SCOTT AVENUE TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_901369_TV18118_JUL2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
18 0929
Downstream MH
18 0928
Dir. of Survey
Downstream
Length Surveyed
351.3 ft.
Total Length
351.3 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
207
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
3
Overall Quick
Overall Rating
345
Pipe schematic from manhole 18 0929 to 18 0928
MH: 18 0929MH: 18 0928downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 18 09292 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start8.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start25.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"28.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"32.6 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"73.5 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"76.3 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"124.2 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"127 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"174.5 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"177.4 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"225.7 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"227.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"275.9 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"279.1 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"323.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"326.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"343.8 ft. H - Hole, at 10 o'clock, within 8 inches of joint: NO345 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"349 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish349 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish351.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0928351.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Hole, at 10 o'clock, within 8 inches of joint: NO

    343.8 ft. - Hole, at 10 o'clock, within 8 inches of joint: NO

  • General Observation - COCKROACHES IN MANHOLE

    351.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (27)

DistanceCodeObservation
0MWM
349CM
227.8TFA
351.3AMH18 0928
127TFA
225.7TFA
76.3TFA
174.5TFA
177.4TFA
326.4TFA
275.9TFC
0MWL
349DAGS
0MGOCOCKROACHES IN MANHOLE
32.6TBA
345TBA
124.2TFA
351.3MGOCOCKROACHES IN MANHOLE
343.8H
0AMH18 0929
279.1TFA
28.5TFC
8.9CM
25.4TFC
323.8TFA
2DAGS
73.5TFA

Properties (7)

additional_info
630069072821201
custom_field_three
HOLE/MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2021-07-28T22:30:01-07:00
documentation
PRO PIPE
is_lateral_inspection
false