Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 5, 2014, 07:56 AM
  • 14 0944_14 0943_05112014_001033.mp4

Date
11/04/2014
W/O
0459312
Weather
Dry
Operator/Surveyor
C. DEHNER
Sewer ID
Z00949
PipeID
P22928
Time
11:56 PM
Certificate
U-912-15963
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1631
Sewer Name
14 TRUNK "F" RELIEF, SECTION 2
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
06
Purpose
Routine Assessment
Project
WO_0459312_TV14052_2014October
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
14 0944
Downstream MH
14 0943
Dir. of Survey
Downstream
Length Surveyed
345.7 ft.
Total Length
345.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3M00
O&M Rating
204
Overall Index
3
Overall Quick
Overall Rating
204
Pipe schematic from manhole 14 0944 to 14 0943
MH: 14 0944MH: 14 0943downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 09440 ft. MWL - Water Level, 25 %of cross sectional area2.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start342.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish345.7 ft. MGO - General Observation - CONNECTION IN MH. @ 9, ACTIVE345.7 ft. AMH - Downstream Manhole, Survey Ends - 14 0943

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0MWM
0AMH14 0944
345.7MGOCONNECTION IN MH. @ 9, ACTIVE
0MWL
342.3DAGS
345.7AMH14 0943
2.7DAGS

Properties (6)

custom_field_two
4
customer
LACSD
datetime
2014-11-04T23:56:51-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
20000114