Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 3, 2014, 12:09 PM
  • 14 0757_14 0756_03112014_043700.mp4

Date
11/03/2014
W/O
0459312
Weather
Dry
Operator/Surveyor
C. DEHNER
Sewer ID
Z00949
PipeID
P20637
Time
4:09 AM
Certificate
U-912-15963
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1629
Sewer Name
14 TRUNK "F" RELIEF, SECTION 2
City
LANCASTER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
WO_0459312_TV14052_2014October
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
14 0757
Downstream MH
14 0756
Dir. of Survey
Downstream
Length Surveyed
290.6 ft.
Total Length
290.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4132
O&M Rating
10
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 14 0757 to 14 0756
MH: 14 0757MH: 14 0756downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 075716.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start286.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish290.6 ft. MGO - General Observation, 8" - Connec, @ Mh, 10 O' Clock. Active290.6 ft. AMH - Downstream Manhole, Survey Ends - 14 0756

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    16.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
290.6MGOConnec, @ Mh, 10 O' Clock. Active
290.6AMH14 0756
0MWM
286.3DAGS
16.7DAGS
0MWL
0AMH14 0757

Properties (6)

custom_field_two
4
customer
LACSD
datetime
2014-11-03T04:09:34-08:00
documentation
PRO-PIPE
is_lateral_inspection
false
year_laid
19921016