Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 1, 2014, 12:57 PM
  • 14 0758_14 0757_01122014_051410.mp4

Date
12/01/2014
W/O
0459312
Weather
Dry
Operator/Surveyor
J .HARTOOG
Sewer ID
Z00949
PipeID
P20638
Time
4:57 AM
Certificate
U507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1684
Sewer Name
14 TRUNK "F" RELIEF, SECTION 2
City
LANCASTER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
WO_0459312_TV14052_2014October
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
14 0758
Downstream MH
14 0757
Dir. of Survey
Downstream
Length Surveyed
269.5 ft.
Total Length
269.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 14 0758 to 14 0757
MH: 14 0758MH: 14 0757downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MANHOLE ACTIVE 7 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 14 0758 (04:57)3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start267.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish269.5 ft. AMH - Downstream Manhole, Survey Ends - 14 0757 (05:12)

Observation photos (3)

  • Water Mark, 40 %of cross sectional area

    0 ft. - Water Mark, 40 %of cross sectional area

  • Upstream Manhole, Survey Begins - 14 0758 (04:57)

    0 ft. - Upstream Manhole, Survey Begins - 14 0758 (04:57)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0MWL
267.3DAGS
3DAGS
269.5AMH14 0757 (05:12)
0MWM
0MGOCONNECTION AT MANHOLE ACTIVE 7 O'CLOCK
0AMH14 0758 (04:57)

Properties (6)

custom_field_two
4
customer
LACSD
datetime
2014-12-01T04:57:05-08:00
documentation
PRO-PIPE
is_lateral_inspection
false
year_laid
19921016