Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 11, 2014, 08:02 AM
  • 32 1178_32 1177_11122014_002347.mpg

Date
12/11/2014
W/O
453976
Weather
Dry
Operator/Surveyor
C. DEHNER
Sewer ID
Z00839
PipeID
P19632
Time
12:02 AM
Certificate
U-912-15963
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2067-SC189994
Sewer Name
32 SAN FERNANDO ROAD TRUNK
City
SANTA CLARITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
07
Purpose
Routine Assessment
Project
WO_453976_TV32022_2014DecemberPackage10
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
32 1178
Downstream MH
32 1177
Dir. of Survey
Downstream
Length Surveyed
514 ft.
Total Length
514 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2S00
O&M Rating
202
Overall Index
2
Overall Quick
Overall Rating
202
Pipe schematic from manhole 32 1178 to 32 1177
MH: 32 1178MH: 32 1177downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 11780 ft. MWM - Water Mark, 20 %of cross sectional area7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start20.6 ft. MGO - General Observation - MAG COATING START117.5 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN149.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN452.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN511.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish511.5 ft. MGO - General Observation - MAG COATING FINISH514 ft. AMH - Downstream Manhole, Survey Ends - 32 1177

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - MAG COATING START

    20.6 ft. - General Observation - MAG COATING START

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN

    117.5 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN

    149.1 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN

    452.3 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN

Observations (11)

DistanceCodeObservation
149.1TBOPEN
117.5TBOPEN
452.3TBOPEN
0MWL
511.5DAGS
7DAGS
514AMH32 1177
511.5MGOMAG COATING FINISH
0AMH32 1178
0MWM
20.6MGOMAG COATING START

Properties (6)

custom_field_two
CR-4
customer
LACSD
datetime
2014-12-11T00:02:57-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
19740129