- Date
- 12/02/2014
- W/O
- 0459292
- Weather
- Dry
- Operator/Surveyor
- J. HARTOOG
- Sewer ID
- Z00950
- PipeID
- P21420
- Time
- 5:27 AM
- Certificate
- U507-03-3386
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K1686-SC189310
- Sewer Name
- 14 TRUNK "F" RELIEF, SECTION 3
- City
- LANCASTER, CA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 14
- Page No.
- 10
- Purpose
- Routine Assessment
- Project
- WO_0459292_TV14051_2014October
- Sewer Type
- GRAVITY
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 18 in.
- Upstream MH
- 14 0841
- Downstream MH
- 14 0840
- Dir. of Survey
- Downstream
- Length Surveyed
- 383 ft.
- Total Length
- 383 ft.
- Structural Index
- 0
- Structural Quick
- 0000
- Structural Rating
- 0
- O&M Index
- 2
- O&M Quick
- 2211
- O&M Rating
- 5
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 5
Pipe schematic from manhole 14 0841 to 14 0840 Observation photos (3)

7 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

112.1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 11 o'clock, , within 8 inches of joint: YES

302.2 ft. - Roots Fine Joint, from 01 to 02 o'clock, within 8 inches of joint: YESR