Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 15, 2014, 09:19 AM
  • 02 1169_02 1166_15122014_014547.mp4

Date
12/15/2014
W/O
453938
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00350
PipeID
P04563
Time
1:19 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K1750-SC190203
Sewer Name
02 GARFIELD AVENUE TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
TV02062
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
02 1169
Downstream MH
02 1166
Dir. of Survey
Downstream
Length Surveyed
30.8 ft.
Total Length
30.8 ft.
Structural Index
4
Structural Quick
4600
Structural Rating
24
O&M Index
2
O&M Quick
4127
O&M Rating
19
Overall Index
3
Overall Quick
Overall Rating
43
Pipe schematic from manhole 02 1169 to 02 1166
MH: 02 1169MH: 02 1166downstream0 ft. VC - Vermin Cockroach, within 8 inches of joint: YES0 ft. AMH - Upstream Manhole, Survey Begins - 02 11690 ft. MWM - Water Mark, 70 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start8.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES10.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES12.1 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"13.7 ft. FM - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES17.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES20.6 ft. OBZ - Obstacles Other, 5 %of cross sectional area, from 07 to 08 o'clock - REBAR20.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES24.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"29 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES30.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish30.8 ft. MSA - Survey Abandoned - DUE TO DEBRIS

Observation photos (8)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    8.3 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    10.7 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"

    12.1 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"

  • Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    13.7 ft. - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    17.7 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Obstacles Other, 5 %of cross sectional area, from 07 to 08 o'clock - REBAR

    20.6 ft. - Obstacles Other, 5 %of cross sectional area, from 07 to 08 o'clock - REBAR

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    20.6 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    29 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
0VC
12.1TB
30.8DAGS
20.6OBZREBAR
30.8MSADUE TO DEBRIS
20.6FM
0AMH02 1169
24.6TFC
29FM
13.7FM
0MWM
0MWL
0DAGS
8.3FM
10.7FM
17.7FM

Properties (5)

custom_field_two
CR 3
customer
LACSD
datetime
2014-12-15T01:19:18-08:00
documentation
PRO PIPE
is_lateral_inspection
false