Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 9, 2014, 05:58 AM
  • 14 0588_14 0587_08122014_221403.mp4

Date
12/08/2014
W/O
453830
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00572
PipeID
P18678
Time
9:58 PM
Certificate
U507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1693
Sewer Name
14 DIVISION STREET TRUNK
City
LANCASTER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
12
Purpose
Routine Assessment
Project
WO#_453830_TV14008_December#6
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
14 0588
Downstream MH
14 0587
Dir. of Survey
Downstream
Length Surveyed
352.9 ft.
Total Length
352.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 14 0588 to 14 0587
MH: 14 0588MH: 14 0587downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 0588 (21:58)87.8 ft. RMJ - Roots Medium Joint, from 03 to 05 o'clock, 5 %, within 8 inches of joint: YESR352.9 ft. MGO - General Observation - CONNECTION AT MANHOLE ACTIVE 3 O'CLOCK352.9 ft. AMH - Downstream Manhole, Survey Ends - 14 0587 (22:13)

Observation photos (3)

  • Water Level, 5 %of cross sectional area

    0 ft. - Water Level, 5 %of cross sectional area

  • Upstream Manhole, Survey Begins - 14 0588 (21:58)

    0 ft. - Upstream Manhole, Survey Begins - 14 0588 (21:58)

  • Roots Medium Joint, from 03 to 05 o'clock, 5 %, within 8 inches of joint: YESR

    87.8 ft. - Roots Medium Joint, from 03 to 05 o'clock, 5 %, within 8 inches of joint: YESR

Observations (6)

DistanceCodeObservation
87.8RMJ
352.9MGOCONNECTION AT MANHOLE ACTIVE 3 O'CLOCK
0MWM
0MWL
352.9AMH14 0587 (22:13)
0AMH14 0588 (21:58)

Properties (6)

custom_field_two
4
customer
LACSD
datetime
2014-12-08T21:58:14-08:00
documentation
PRO-PIPE
is_lateral_inspection
false
year_laid
19810624