Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 9, 2014, 06:48 AM
  • 14 0586_14 0585_08122014_231121.mp4

Date
12/08/2014
W/O
453830
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00572
PipeID
P18675
Time
10:48 PM
Certificate
U507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1693
Sewer Name
14 DIVISION STREET TRUNK
City
LANCASTER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
12
Purpose
Routine Assessment
Project
WO#_453830_TV14008_December#6
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
14 0586
Downstream MH
14 0585
Dir. of Survey
Downstream
Length Surveyed
330 ft.
Total Length
330 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
3
Pipe schematic from manhole 14 0586 to 14 0585
MH: 14 0586MH: 14 0585downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 0586 (22:49)0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start156.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"266.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"328.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish329.9 ft. MGO - General Observation - CONNECTION AT MANHOLE ACTIVE 3 O'CLOCK330 ft. VC - Vermin Cockroach, within 8 inches of joint: NO - >50330 ft. AMH - Downstream Manhole, Survey Ends - 14 0585 (23:10)

Observation photos (6)

  • Upstream Manhole, Survey Begins - 14 0586 (22:49)

    0 ft. - Upstream Manhole, Survey Begins - 14 0586 (22:49)

  • Water Mark, 15 %of cross sectional area

    0 ft. - Water Mark, 15 %of cross sectional area

  • Water Level, 10 %of cross sectional area

    0 ft. - Water Level, 10 %of cross sectional area

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    156.8 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    266.2 ft. - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"

Observations (10)

DistanceCodeObservation
330VC>50
328.2DAGS
2.1DAGS
0AMH14 0586 (22:49)
329.9MGOCONNECTION AT MANHOLE ACTIVE 3 O'CLOCK
0MWM
0MWL
266.2TBA
330AMH14 0585 (23:10)
156.8TFC

Properties (6)

custom_field_two
4
customer
LACSD
datetime
2014-12-08T22:48:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false
year_laid
19810624