Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 9, 2014, 12:16 PM
  • 14 0529_14 0528_20141209_055652.mp4

Date
12/09/2014
W/O
443102
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00574
PipeID
P18008
Time
4:16 AM
Certificate
U507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1695
Sewer Name
14 LANCASTER BOULEVARD TRUNK
City
LANCASTER, CA
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
07
Purpose
Routine Assessment
Project
WO#_443102_TV14011_December#6
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
14 0529
Downstream MH
14 0528
Dir. of Survey
Downstream
Length Surveyed
337.6 ft.
Total Length
337.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
4
O&M Quick
5131
O&M Rating
8
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 14 0529 to 14 0528
MH: 14 0529MH: 14 0528downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 0529 (04:17)0 ft. MWM - Water Mark, 5 %of cross sectional area133.2 ft. DSF - Deposits Settled Fine, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start337.6 ft. DSF - Deposits Settled Fine, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish337.6 ft. DSF - Deposits Settled Fine, 45 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO337.6 ft. MSA - Survey Abandoned - DUE TO DEPOSITS SETTLED FINE BLOCKING ENTRANCE TO MANHOLE

Observation photos (2)

  • Deposits Settled Fine,  15 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    133.2 ft. - Deposits Settled Fine, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Settled Fine,  45 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: NO

    337.6 ft. - Deposits Settled Fine, 45 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO

Observations (7)

DistanceCodeObservation
0MWL
0AMH14 0529 (04:17)
337.6DSF
337.6DSF
337.6MSADUE TO DEPOSITS SETTLED FINE BLOCKING ENTRANCE TO MANHOLE
133.2DSF
0MWM

Properties (6)

additional_info
SC189319
custom_field_two
4
customer
LACSD
datetime
2014-12-09T04:16:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false