Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 28, 2021, 07:03 AM
  • 22 1457_22 1084_07282021_002557.mp4

Date
07/28/2021
W/O
901759
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00812
PipeID
P17458
Time
12:03 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9105
Sewer Name
22 IRWINDALE TRUNK, SECTS 2,3,4,&5
City
AZUSA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_901759_TV22043_JUL2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 1084
Downstream MH
22 1457
Dir. of Survey
Upstream
Length Surveyed
315 ft.
Total Length
315 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
150
O&M Index
2
O&M Quick
312K
O&M Rating
119
Overall Index
2
Overall Quick
Overall Rating
269
Pipe schematic from manhole 22 1084 to 22 1457
MH: 22 1084MH: 22 1457upstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 14570 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish2.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish73.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"96.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"165.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"178.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"216.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"226.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"229.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"251.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start291.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start298.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"301.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"307.9 ft. TBD - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: YES, 6", 6"315 ft. AMH - Downstream Manhole, Survey Begins - 22 1084315 ft. MWL - Water Level, 5 %of cross sectional area315 ft. MWM - Water Mark, 15 %of cross sectional area

Observation photos (4)

  • Tap Break-In Defective, at 10 o'clock, -,  , within 8 inches of joint: YES, 6", 6"

    7.1 ft. - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: YES, 6", 6"

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    23.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    63.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    88.5 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

Observations (19)

DistanceCodeObservation
0AMH22 1084
23.8DAGS
7.1TBD
312.9DAGS
149.5TFC
13.5TFC
88.5TB
136.5TFC
218.1TFC
312.9CM
0MWL
0MWM
63.1CM
98.1TF
85.3TFC
241.2TFC
315AMH22 1457
315MGOCONNECTION AT MH, 3 O'CLOCK
16.3TFC

Properties (7)

additional_info
630075072721202
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-07-28T00:03:34-07:00
documentation
PRO PIPE
is_lateral_inspection
false