Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 28, 2021, 07:54 AM
  • 22 1079_22 1078_07282021_012107.mp4

Date
07/28/2021
W/O
901759
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00812
PipeID
P17452
Time
12:54 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9105
Sewer Name
22 IRWINDALE TRUNK, SECTS 2,3,4,&5
City
AZUSA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_901759_TV22043_JUL2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 1078
Downstream MH
22 1079
Dir. of Survey
Upstream
Length Surveyed
411.5 ft.
Total Length
411.5 ft.
Structural Index
3
Structural Quick
423O
Structural Rating
245
O&M Index
2
O&M Quick
322O
O&M Rating
170
Overall Index
3
Overall Quick
Overall Rating
415
Pipe schematic from manhole 22 1078 to 22 1079
MH: 22 1078MH: 22 1079upstream0 ft. MGO - General Observation - CONNECTION AT MH 2 OCLOCK CAPPED0 ft. AMH - Upstream Manhole, Survey Ends - 22 10790 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK0.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish83.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"85.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6"109 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"113.6 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 6"126.2 ft. FM - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES147.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES157.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"160 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"198.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"234.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"236.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"300.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"308.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"328.2 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 6"328.2 ft. B - Broken, from 12 to 02 o'clock, within 8 inches of joint: YES341.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"362.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"374.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"387.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"388.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start409.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start411.5 ft. AMH - Downstream Manhole, Survey Begins - 22 1078411.5 ft. MWL - Water Level, 10 %of cross sectional area411.5 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK411.5 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (9)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    22.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    69.8 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Defective, at 02 o'clock, -,  , within 8 inches of joint: YES, 6"

    83.3 ft. - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 6"

  • Broken, from 12 to 02 o'clock, within 8 inches of joint: YES

    83.3 ft. - Broken, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    213.1 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    264.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

    285.3 ft. - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

  • Tap Break-In Defective, at 02 o'clock, -,  , within 8 inches of joint: YES, 6"

    297.9 ft. - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 6"

Observations (31)

DistanceCodeObservation
0AMH22 1078
36.7TFC
264.4FL
174.7TF
411.5MGOCONNECTION AT MH 2 OCLOCK CAPPED
0MWL
411.5AMH22 1079
69.8TB
254.1TFC
111.1TFC
411.5MGOCONNECTION AT MH, 3 O'CLOCK
0MGOCONNECTION AT MH, 3 O'CLOCK
0MWM
410.9DAGS
411.5MGOCONNECTION AT MH, 9 O'CLOCK
22.6CM
2DAGS
328.2TFC
83.3TBD
213.1TB
83.3B
285.3FM
49.4TFC
177.4TFC
24TFC
103.3TFC
297.9TBD
410.9CM
302.5TFC
325.8TF
251.5TFC

Properties (7)

additional_info
630075072721202
custom_field_three
broken, cracks fractures
custom_field_two
2
customer
1
datetime
2021-07-28T00:54:40-07:00
documentation
PRO PIPE
is_lateral_inspection
false