Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 9, 2021, 08:50 AM
  • 02 1772_02 1771_892021_020046.mp4

Date
08/09/2021
W/O
0890811
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00271
PipeID
P04119
Time
1:50 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1906
Sewer Name
02 INDIANA STREET TRUNK
City
LOS ANGLES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
07A
Purpose
Routine Assessment
Project
20210805MDM_INDIANA_STREET_TRUNK
Material
NRCP
Shape
Circular
Height
7.570000171661377 in.
Upstream MH
02 1772
Downstream MH
02 1771
Dir. of Survey
Downstream
Length Surveyed
353.7 ft.
Total Length
353.7 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 02 1772 to 02 1771
MH: 02 1772MH: 02 1771downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:50AM0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - FIBOROUS BLISTERING OUTER SUFACE78.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Open94.4 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Active170.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 5" - Open229.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Open272.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Open285.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Open353.1 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish - FIBOROUS BLISTERING353.7 ft. AMH - Downstream Manhole, Survey Ends - 2:35AM

Observation photos (1)

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - FIBOROUS BLISTERING OUTER SUFACE

    2 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - FIBOROUS BLISTERING OUTER SUFACE

Observations (12)

DistanceCodeObservation
229.2TBOpen
78.8TBOpen
0MWL
2SSSFIBOROUS BLISTERING OUTER SUFACE
272.6TBOpen
0AMH1:50AM
0MWM
170.7TBOpen
353.7AMH2:35AM
94.4TBAActive
353.1SSSFIBOROUS BLISTERING
285.1TBOpen

Properties (7)

custom_field_three
SPALLING FIBOROUS OUTER SURFACE
custom_field_two
4
customer
LACSD
datetime
2021-08-09T01:50:00-07:00
documentation
MARTIN,REVELES,BARR,RAMERIZ
is_lateral_inspection
false
lining
CIPP