03 0363_03 0362_862021_042326.mp4
2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG
2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR CORRODED AND MISSING
8 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR
16.6 ft. - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR
28 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR MISSING
63 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR MISSING
94.8 ft. - Water Level, 30 %of cross sectional area
118.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR
124.2 ft. - Infiltration Runner, from 10 to 02 o'clock, within 8 inches of joint: YES
| Distance | Code | Observation |
|---|---|---|
| 2 | IR | — |
| 2 | DSZ | SLUDGE ROCKS |
| 2 | SAM | SEVERE AGG |
| 16.6 | SRC | CIRCUM REBAR |
| 51.8 | TFA | Active |
| 180.3 | MGO | Conn. @ Mh, 9 O' Clock. Active |
| 0 | MWL | — |
| 124.2 | IR | — |
| 0 | MWM | — |
| 180.3 | SRC | LOMG & CIRCUM REBAR CORRODED & MISSING |
| 0 | AMH | 4:20AM |
| 94.8 | MWL | — |
| 180.7 | AMH | 5:00AM |
| 8 | SRV | CIRCUM REBAR |
| 130 | IR | — |
| 0 | MGO | Conn. @ Mh, 9 O' Clock. Active |
| 180.3 | DSZ | SLUDGE & ROCKS |
| 110.7 | TF | Open |
| 118.7 | SRC | LONG CIRCUM REBAR |
| 155.6 | TFA | Active |
| 2 | SRC | LONG & CIRCUM REBAR CORRODED AND MISSING |
| 180.2 | SAM | SEVERE AGG |
| 63 | SRC | LONG CIRCUM REBAR MISSING |
| 57.3 | IR | — |
| 28 | SRC | CIRCUM REBAR MISSING |
| 180.3 | MGO | POSSIBLE CORRISON BELOW WATER MARK |