Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 15, 2021, 09:34 AM
  • 32 0069_32 0068_07152021_024554.mp4

Date
07/15/2021
W/O
901760
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00886
PipeID
P19833
Time
2:34 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9032
Sewer Name
32 CASTAIC TRUNK
City
CASTAIC
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_901760_TV32047_JUL2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0069
Downstream MH
32 0068
Dir. of Survey
Downstream
Length Surveyed
192.3 ft.
Total Length
192.3 ft.
Structural Index
4
Structural Quick
5141
Structural Rating
15
O&M Index
2
O&M Quick
2G00
O&M Rating
76
Overall Index
2
Overall Quick
Overall Rating
91
Pipe schematic from manhole 32 0069 to 32 0068
MH: 32 0069MH: 32 0068downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 00690 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start68.5 ft. FS - Fracture Spiral, from 06 to 09 o'clock, within 8 inches of joint: YES74.9 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES96.5 ft. RPL - Repair Localized Liner, within 8 inches of joint: YES, Start102.5 ft. RPL - Repair Localized Liner, within 8 inches of joint: YES, Finish117.2 ft. FS - Fracture Spiral, from 09 to 03 o'clock, within 8 inches of joint: YES148.2 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES190.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish192.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE192.3 ft. AMH - Downstream Manhole, Survey Ends - 32 0068

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Spiral, from 06 to 09 o'clock, within 8 inches of joint: YES

    68.5 ft. - Fracture Spiral, from 06 to 09 o'clock, within 8 inches of joint: YES

  • Broken, from 10 to 02 o'clock, within 8 inches of joint: YES

    74.9 ft. - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Repair Localized Liner, within 8 inches of joint: YES, Start

    96.5 ft. - Repair Localized Liner, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 09 to 03 o'clock, within 8 inches of joint: YES

    117.2 ft. - Fracture Spiral, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    148.2 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    192.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (13)

DistanceCodeObservation
74.9B
190.4DAGS
0AMH32 0069
117.2FS
192.3MGOCOCKROACHES IN MANHOLE
192.3AMH32 0068
0MWL
68.5FS
2DAGS
148.2FM
96.5RPL
0MWM
102.5RPL

Properties (8)

additional_info
630069071421202
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2021-07-15T02:34:15-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
27282