Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 12, 2021, 09:53 AM
  • 18 0867_18 0866_07122021_030024.mp4

Date
07/12/2021
W/O
896356
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00709
PipeID
P14719
Time
2:53 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8998
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
SANTA FE SPRINGS
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
35
Purpose
Routine Assessment
Project
WO_896356_TV18101_JUN2021
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
18 0866
Downstream MH
18 0867
Dir. of Survey
Upstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 18 0866 to 18 0867
MH: 18 0866MH: 18 0867upstream0 ft. MSA - Survey Abandoned - VIEW OF U/S SIPHON FROM D/S MH0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES0 ft. MGO - General Observation - MAG COAT2 ft. MWL - Water Level, 30 %of cross sectional area2 ft. AMH - Downstream Manhole, Survey Begins - 18 08662 ft. MWM - Water Mark, 70 %of cross sectional area

Observation photos (3)

  • Survey Abandoned - VIEW OF U/S SIPHON FROM D/S MH

    2 ft. - Survey Abandoned - VIEW OF U/S SIPHON FROM D/S MH

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

Observations (6)

DistanceCodeObservation
0MWL
0AMH18 0866
2MSAVIEW OF U/S SIPHON FROM D/S MH
2SSS
0MWM
2MGOMAG COAT

Properties (8)

additional_info
630074070921062
custom_field_three
SPALLING, MAG COAT
custom_field_two
3
customer
1
datetime
2021-07-12T02:53:55-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
43843