Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 9, 2021, 05:13 PM
  • 18 0870_18 0868_07092021_103253.mp4

Date
07/09/2021
W/O
896356
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00709
PipeID
P14721
Time
10:13 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
k9068
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
35
Purpose
Routine Assessment
Project
WO_896356_TV18101_JUN2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
18 0870
Downstream MH
18 0868
Dir. of Survey
Downstream
Length Surveyed
581 ft.
Total Length
581 ft.
Structural Index
2
Structural Quick
3V2V
Structural Rating
571
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
571
Pipe schematic from manhole 18 0870 to 18 0868
MH: 18 0870MH: 18 0868downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 08700 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2.1 ft. MGO - General Observation - MAG COAT2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start581 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish581 ft. AMH - Downstream Manhole, Survey Ends - 18 0868581 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK581 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    16.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
581SAP
2.1MGOMAG COAT
0AMH18 0870
0MGOCONNECTION AT THE MH 9 OC'LOCK
0MWM
0MWL
2.1SSS
581AMH18 0868
581MGOCONNECTION AT THE MH 3 OC'LOCK
16.9SAP
581SSS

Properties (7)

additional_info
630074070921062
custom_field_three
SPALLING/AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2021-07-09T10:13:55-07:00
documentation
PROPIPE
is_lateral_inspection
false