Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 9, 2021, 05:35 PM
  • 18 0868_18 0867_07092021_105644.mp4

Date
07/09/2021
W/O
896356
Weather
Dry
Operator/Surveyor
b.fugate
Sewer ID
Z00709
PipeID
P14720
Time
10:35 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9068
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
santa fe springs
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
35
Purpose
Routine Assessment
Project
WO_896356_TV18101_JUN2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
18 0868
Downstream MH
18 0867
Dir. of Survey
Downstream
Length Surveyed
544 ft.
Total Length
544 ft.
Structural Index
3
Structural Quick
3U2U
Structural Rating
540
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
540
Pipe schematic from manhole 18 0868 to 18 0867
MH: 18 0868MH: 18 0867downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 08680 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.5 ft. MGO - General Observation - MAG COAT2.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start111.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"117.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"149 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"207.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"261 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"307.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"355.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"370.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"411.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"543.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish543.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish544 ft. AMH - Downstream Manhole, Survey Ends - 18 0867

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
543.6SSS
355.2TFC
543.6SAP
207.9TFC
149TF
0AMH18 0868
411.4TF
544AMH18 0867
0MGOCONNECTION AT THE MH 3 OC'LOCK
0MWM
370.9TFC
307.3TFC
117.6TF
2.5MGOMAG COAT
0MWL
2.6SSS
2.6SAP
111.8TF
261TF

Properties (7)

additional_info
630074070921062
custom_field_three
SPALLING/AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2021-07-09T10:35:39-07:00
documentation
PROPIPE
is_lateral_inspection
false