Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 9, 2021, 05:57 PM
  • 18 0867_18 0866_07092021_110108.mp4

Date
07/09/2021
W/O
896356
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00709
PipeID
P14719
Time
10:57 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9068
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
SANTA FE SPRINGS
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
35
Purpose
Routine Assessment
Project
WO_896356_TV18101_JUN2021
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
18 0867
Downstream MH
18 0866
Dir. of Survey
Downstream
Length Surveyed
2.8 ft.
Total Length
2.8 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 18 0867 to 18 0866
MH: 18 0867MH: 18 0866downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 08670 ft. MWL - Water Level, 30 %of cross sectional area2.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES2.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES2.8 ft. MSA - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.2.8 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

    2.8 ft. - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.8 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
0MWM
2.8SAP
2.8SSS
2.8MSAVIEW OF DOWNLEG OF U/S SIPHON.
0AMH18 0867
0MWL
2.8SRV

Properties (8)

additional_info
630074070921062
custom_field_three
REINFORCEMENT VISIBLE/AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2021-07-09T10:57:56-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
43843