Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 9, 2021, 08:20 AM
  • 18 0856_18 0855_07092021_014717.mp4

Date
07/09/2021
W/O
896356
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00709
PipeID
P14711
Time
1:20 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9027
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
34
Purpose
Routine Assessment
Project
WO_896356_TV18101_JUN2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Width
51 in.
Upstream MH
18 0856
Downstream MH
18 0855
Dir. of Survey
Downstream
Length Surveyed
724 ft.
Total Length
724 ft.
Structural Index
3
Structural Quick
5C3\
Structural Rating
830
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
834
Pipe schematic from manhole 18 0856 to 18 0855
MH: 18 0856MH: 18 0855downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 08562 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start95.5 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"109.7 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish389 ft. MGO - General Observation - MAG COATING THROUGHOUT723 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish723 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish724 ft. MGO - General Observation - COCKROACHES IN MANHOLE724 ft. AMH - Downstream Manhole, Survey Ends - 18 0855

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COATING THROUGHOUT

    389 ft. - General Observation - MAG COATING THROUGHOUT

  • General Observation - COCKROACHES IN MANHOLE

    724 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
723SSS
109.7SRV
0MGOCOCKROACHES IN MANHOLE
95.5TBA
2SRV
389MGOMAG COATING THROUGHOUT
0MWL
723SAP
0MWM
2SSS
0AMH18 0856
724MGOCOCKROACHES IN MANHOLE
724AMH18 0855
2SAP

Properties (7)

additional_info
630069070821201
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-07-09T01:20:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false