Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 2, 2015, 11:01 AM
  • H 0236_H 0235_20151002_030645.mp4

Date
10/02/2015
W/O
521014
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00171
PipeID
P10655
Time
4:01 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2694
Sewer Name
H JOINT OUTFALL H - UNIT 2F
City
VERNON
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
16
Purpose
Routine Assessment
Project
WO_521014_TV02170_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
H 0235
Downstream MH
H 0236
Dir. of Survey
Upstream
Length Surveyed
50.7 ft.
Total Length
50.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole H 0235 to H 0236
MH: H 0235MH: H 0236upstream0 ft. AMH - Upstream Manhole, Survey Ends - H 02360 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - APPED CONNECTION AT MH 3 O'CLOCK48.7 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start50.7 ft. MWL - Water Level, 10 %of cross sectional area50.7 ft. MWM - Water Mark, 15 %of cross sectional area50.7 ft. AMH - Downstream Manhole, Survey Begins - H 0235

Observation photos (1)

  • Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0MWL
0MWM
2DAGS
50.7AMHH 0236
50.7DAGS
0AMHH 0235
50.7MGOAPPED CONNECTION AT MH 3 O'CLOCK

Properties (6)

additional_info
SC203917
custom_field_two
4
customer
LACSD
datetime
2015-10-02T04:01:53-07:00
documentation
PRO PIPE
is_lateral_inspection
false