Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 13, 2015, 08:59 AM
  • H 0238_H 0237_20151013_011643.mp4

Date
10/13/2015
W/O
521014
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00171
PipeID
P10656
Time
1:59 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2705
Sewer Name
H JOINT OUTFALL H - UNIT 2F
City
VERNON
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
16
Purpose
Routine Assessment
Project
WO_521014_TV02170_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
H 0238
Downstream MH
H 0237
Dir. of Survey
Downstream
Length Surveyed
101.4 ft.
Total Length
101.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole H 0238 to H 0237
MH: H 0238MH: H 0237downstream0 ft. MGO - General Observation - CONNECTION AT MH 4 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - H 02380 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start44 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"100.3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish101.4 ft. AMH - Downstream Manhole, Survey Ends - H 0237

Observation photos (1)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
44TF
0MGOCONNECTION AT MH 4 O'CLOCK
0AMHH 0238
101.4AMHH 0237
0MWM
100.3DAGS
2DAGS
0MWL

Properties (6)

additional_info
SC203928
custom_field_two
4
customer
LACSD
datetime
2015-10-13T01:59:16-07:00
documentation
PRO PIPE
is_lateral_inspection
false