Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 2, 2015, 07:50 AM
  • H 0225_H 0224_20151002_000422.mp4

Date
10/02/2015
W/O
521014
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00171
PipeID
P10642
Time
12:50 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2694
Sewer Name
H JOINT OUTFALL H - UNIT 2F
City
BELL
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
WO_521014_TV02170_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
H 0224
Downstream MH
H 0225
Dir. of Survey
Upstream
Length Surveyed
329.9 ft.
Total Length
329.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole H 0224 to H 0225
MH: H 0224MH: H 0225upstream0 ft. AMH - Upstream Manhole, Survey Ends - H 02250 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish55 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"157 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"174.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start257.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"329.9 ft. AMH - Downstream Manhole, Survey Begins - H 0224329.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start329.9 ft. MWM - Water Mark, 15 %of cross sectional area329.9 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (1)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0AMHH 0224
329.9AMHH 0225
274.9TFC
155.3CM
0DAGS
329.9CM
0MWM
0MWL
329.9DAGS
172.9TFC
72.8TFC

Properties (6)

additional_info
SC203917
custom_field_two
3
customer
LACSD
datetime
2015-10-02T00:50:49-07:00
documentation
PRO PIPE
is_lateral_inspection
false