Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 2, 2015, 06:24 AM
  • H 0228_H 0227_20151001_223745.mp4

Date
10/01/2015
W/O
521014
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00171
PipeID
P10645
Time
11:24 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2694
Sewer Name
H JOINT OUTFALL H - UNIT 2F
City
BELL
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
WO_521014_TV02170_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
H 0228
Downstream MH
H 0227
Dir. of Survey
Downstream
Length Surveyed
328.4 ft.
Total Length
328.4 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
2
Overall Quick
Overall Rating
136
Pipe schematic from manhole H 0228 to H 0227
MH: H 0228MH: H 0227downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 02280 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start29.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start43.1 ft. RPZ - Repair Other, within 8 inches of joint: YES - HOLE WITH REPAIR49.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"147.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"327.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish327.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish328.4 ft. AMH - Downstream Manhole, Survey Ends - H 0227328.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (2)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Repair Other, within 8 inches of joint: YES - HOLE WITH REPAIR

    43.1 ft. - Repair Other, within 8 inches of joint: YES - HOLE WITH REPAIR

Observations (12)

DistanceCodeObservation
328.4AMHH 0227
327.1CM
328.4MGOCONNECTION AT MH 3 O'CLOCK
0MWL
147.7TFC
2DAGS
327.1DAGS
29.7CM
49.1TFC
43.1RPZHOLE WITH REPAIR
0AMHH 0228
0MWM

Properties (6)

additional_info
SC203917
custom_field_two
3
customer
LACSD
datetime
2015-10-01T23:24:53-07:00
documentation
PRO PIPE
is_lateral_inspection
false