Wastewater/Activity/PacpInspection/1.0Sep 30, 2015, 08:25 AM
  • H 0231_H 0230_20150930_022755.mp4

Date
09/30/2015
W/O
521014
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00171
PipeID
P10648
Time
1:25 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2692
Sewer Name
H JOINT OUTFALL H - UNIT 2F
City
VERNON
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
WO_521014_TV02170_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
H 0231
Downstream MH
H 0230
Dir. of Survey
Downstream
Length Surveyed
336.1 ft.
Total Length
336.1 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
99
O&M Index
2
O&M Quick
2L00
O&M Rating
134
Overall Index
2
Overall Quick
Overall Rating
233
Pipe schematic from manhole H 0231 to H 0230
MH: H 0231MH: H 0230downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - H 02312 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start21.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"121.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"170.8 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start221 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"323 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"336.1 ft. AMH - Downstream Manhole, Survey Ends - H 0230336.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish336.1 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
336.1AMHH 0230
336.1DAGS
0MWM
221TFC
0MWL
121.9TFC
336.1CM
323TFC
0MGOCOCKROACHES IN MANHOLE
170.8CM
0AMHH 0231
21.3TFC
2DAGS

Properties (6)

additional_info
SC203915
custom_field_two
3
customer
LACSD
datetime
2015-09-30T01:25:30-07:00
documentation
PRO PIPE
is_lateral_inspection
false