Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 23, 2015, 07:26 AM
  • 01 0559_01 0558_20150122_234330.mp4

Date
01/22/2015
W/O
486126
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00194
PipeID
P01046
Time
11:26 PM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2117
Sewer Name
01 ALAMEDA STREET EXTENSION TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_486126_TV01001_2015JANUARY
Sewer Type
GRAVITY
Material
NRCP
Lining Method
Segmented Panel
Shape
Circular
Height
21 in.
Upstream MH
01 0559
Downstream MH
01 0558
Dir. of Survey
Downstream
Length Surveyed
399.2 ft.
Total Length
399.2 ft.
Structural Index
3
Structural Quick
3N00
Structural Rating
222
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
222
Pipe schematic from manhole 01 0559 to 01 0558
MH: 01 0559MH: 01 0558downstream0 ft. MGO - General Observation - Magnesium hydroxide coating 40%start0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 055925.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start396.9 ft. MGO - General Observation - Magnesium hydroxide coating 40% finish396.9 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish399.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0558

Observations (8)

DistanceCodeObservation
396.9MGOMagnesium hydroxide coating 40% finish
0MGOMagnesium hydroxide coating 40%start
396.9SAV
25.1SAV
399.2AMH01 0558
0MWL
0MWM
0AMH01 0559

Properties (6)

additional_info
SC190227
custom_field_two
4
customer
LACSD
datetime
2015-01-22T23:26:14-08:00
documentation
PRO PIPE
is_lateral_inspection
false