- Date
- 07/19/2021
- W/O
- 901239
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00629
- PipeID
- P12417
- Time
- 3:48 AM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K9037
- Sewer Name
- 15 SANTA ANITA OUTFALL TRUNK
- City
- ROSEMEAD
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 21
- Purpose
- Routine Assessment
- Project
- RFIR_WO_901239_TV15144_JUL2021
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 21 in.
- Width
- 21 in.
- Upstream MH
- 15 0492
- Downstream MH
- 15 0491
- Dir. of Survey
- Downstream
- Length Surveyed
- 253.4 ft.
- Total Length
- 253.4 ft.
- Structural Index
- 2
- Structural Quick
- 2I00
- Structural Rating
- 100
- O&M Index
- 2
- O&M Quick
- 312I
- O&M Rating
- 103
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 203
Pipe schematic from manhole 15 0492 to 15 0491 Observation photos (4)

0 ft. - General Observation - ROACHES @ MH

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

203.4 ft. - Tap Break-In Defective, at 12 o'clock, -, , within 8 inches of joint: YES, 6" - ACTIVE

253.4 ft. - General Observation - ROACHES @ MH