- Date
- 07/26/2021
- W/O
- 901693
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00177
- PipeID
- P10804
- Time
- 3:12 AM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K9044
- Sewer Name
- H JOINT OUTFALL H - UNIT 5A
- City
- PICO RIVERA
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 06
- Purpose
- Routine Assessment
- Project
- RFIR_WO_901693_TV15225_JUL2021
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 66 in.
- Width
- 66 in.
- Upstream MH
- H 0375
- Downstream MH
- H 0342
- Dir. of Survey
- Downstream
- Length Surveyed
- 961.3 ft.
- Total Length
- 961.3 ft.
- Structural Index
- 3
- Structural Quick
- 5138
- Structural Rating
- 29
- O&M Index
- 4
- O&M Quick
- 4100
- O&M Rating
- 4
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 33
Pipe schematic from manhole H 0375 to H 0342 Observation photos (4)

0 ft. - General Observation - FLOW METER AT MH

2 ft. - General Observation - MAG COATING THROUGHOUT

920.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

959.2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES