Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 12, 2021, 11:22 AM
  • 03 0002_03 0001_07122021_044905.mp4

Date
07/12/2021
W/O
901268
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00366
PipeID
P05020
Time
4:22 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8675
Sewer Name
03 LOS COYOTES DIAGONAL TRUNK
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_901268_TV03170_JUL2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
30 in.
Upstream MH
03 0002
Downstream MH
03 0001
Dir. of Survey
Downstream
Length Surveyed
340.8 ft.
Total Length
340.8 ft.
Structural Index
3
Structural Quick
4237
Structural Rating
39
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
41
Pipe schematic from manhole 03 0002 to 03 0001
MH: 03 0002MH: 03 0001downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 00020 ft. MWL - Water Level, 10 %of cross sectional area2.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start13.1 ft. CM - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES51.7 ft. FM - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES - FROM CONNECTION51.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"79.2 ft. CM - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES90.9 ft. CM - Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES109.5 ft. FS - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES137.5 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES158.5 ft. FM - Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES195 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES200.4 ft. CS - Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES214.5 ft. CS - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES222.4 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES242.8 ft. CS - Crack Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES245.6 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"295 ft. CM - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES304 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start340.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish340.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish340.8 ft. AMH - Downstream Manhole, Survey Ends - 03 0001

Observation photos (15)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

    13.1 ft. - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES - FROM CONNECTION

    51.7 ft. - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES - FROM CONNECTION

  • Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    79.2 ft. - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    90.9 ft. - Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES

    109.5 ft. - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    137.5 ft. - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

    158.5 ft. - Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    195 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

    200.4 ft. - Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    214.5 ft. - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    222.4 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES

    242.8 ft. - Crack Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

    295 ft. - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    304 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
51.7FMFROM CONNECTION
195CL
0MWM
0AMH03 0002
214.5CS
13.1CM
200.4CS
340.8AMH03 0001
295CM
222.4CS
340.6DAGS
51.7TB
2.6DAGS
0MWL
245.6TBA
340.5CM
242.8CS
90.9CM
137.5CM
109.5FS
304CM
79.2CM
158.5FM

Properties (6)

custom_field_three
CRACKS, FRACTURES
custom_field_two
2
customer
1
datetime
2021-07-12T04:22:14-07:00
documentation
PROPIPE
is_lateral_inspection
false