Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 20, 2021, 05:16 AM
  • B 0373_B 0372_07192021_222733.mp4

Date
07/19/2021
W/O
901610
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00091
PipeID
P08885
Time
10:16 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9038
Sewer Name
B JOINT OUTFALL B - UNIT 5A
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
10
Purpose
Routine Assessment
Project
WO_901610_TV15051_JUL2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
60 in.
Upstream MH
B 0373
Downstream MH
B 0372
Dir. of Survey
Downstream
Length Surveyed
331.4 ft.
Total Length
331.4 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
315
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
319
Pipe schematic from manhole B 0373 to B 0372
MH: B 0373MH: B 0372downstream0 ft. MGO - General Observation - MAG COATING THROUGHOUT0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 03732 ft. MGO - General Observation - MAG COATING THROUGHOUT12.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start12.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start329.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish329.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish331.4 ft. AMH - Downstream Manhole, Survey Ends - B 0372331.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (4)

  • General Observation - MAG COATING THROUGHOUT

    0 ft. - General Observation - MAG COATING THROUGHOUT

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    12.3 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    331.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
0MGOMAG COATING THROUGHOUT
329.4SAP
0MWL
2MGOMAG COATING THROUGHOUT
329.4SSS
0MWM
0AMHB 0373
12.2SSS
12.3SAP
331.4AMHB 0372
331.4MGOCOCKROACHES IN MANHOLE

Properties (7)

additional_info
630069071921201
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-07-19T22:16:04-07:00
documentation
PRO PIPE
is_lateral_inspection
false